How we worked it out
Updated as you change the numbers.
- Resistance of 12 AWG copper at 75 °C ≈ 1.9315 Ω per 1,000 ft.
- Drop = 2 × length × current × resistance ÷ 1,000.
Method and assumptions
Resistance comes from the conductor’s cross-section (from the AWG formula) and resistivity at 75 °C, matching NEC Chapter 9 Table 8 values to within about 2%. Single-phase drop counts both wires (2 × one-way length); three-phase uses √3. The NEC’s informational notes suggest at most 3% on a branch circuit and 5% in total.
Questions
What is the voltage drop on 100 ft of 12 AWG copper at 16 A, 120 V?
About 6.2 V, or 5.2%, so 10 AWG would be a better choice.